Tripp Lite SU40K SmartOnline Modular 3-Phase UPS System

Tripp Lite Updated: 2009-01-25 RSS
Tripp Lite SU40K SmartOnline Modular 3-Phase UPS System

Tripp Lite's SU40K (40kVA) SmartOnline Modular 3-Phase Intelligent, True On-Line UPS System provides 100% system availability with N+1 modular architecture and 1+1 parallel capability. In an N+1 configuration, the SU40K provides two self-contained, redundant 20kVA power modules that can be hot-swapped (with the load powered) if maintenance is required. Connect two SU40K models in parallel (1+1 configuration) to provide fail-safe redundancy (two 40kVA models supporting a 40kVA load) or to increase capacity (two 40kVA models supporting an 80kVA load).

The SU40K provides mission-critical equipment with the highest level of power protection available. Large capacity 40,000VA/32,000W UPS continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with zero transfer time assures compatibility with all equipment types. The SU40K's high input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology produce less than 3% input Total Harmonic Distortion (THDi). With low THDi, generators run cooler and last longer, allowing managers to save installation costs by installing a generator with a capacity equal to the equipment load (1:1 ratio). Extremely efficient operation (up to 96%) saves money by lowering electricity consumption. Hardwire input and output connections support a variety of permanent or PDU-style power connections. The SU40K features 120/208V AC, 3-phase, 4-wire (plus ground), wye input and output. It also features a wide input voltage correction range: 94-150/163-260V AC. Frequency is 50 or 60 Hz (auto-selectable). The SU40K combines internal power and battery components in a single small-footprint tower module. Typical half-load/full-load runtimes are 13 min./5.5 min. Battery runtime can be extended with optional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C with matching battery cabinets, available separately). Additional battery cabinets for extended runtime solutions also available; contact Tripp Lite for more information. A manual bypass breaker and an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power if the UPS requires maintenance. A built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server. An accessory slot accepts an optional internal SNMP card (Model SNMPWEBCARD) for remote shutdowns, reboots and more. Front panel combination LCD/LED display alerts users to a variety of UPS operational modes and conditions. The LCD display includes a real-time event log screen with up to 500 events listed. A dynamic battery management screen optimizes battery function to lengthen service life and allows cold restart of the UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns the UPS output OFF and disables Bypass output. Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities. A 1-year limited repair warranty is included. A start-up service program is recommended to enhance the reliability of the installation.

* N+1 configuration: two self-contained, redundant 20kVA power modules can be hot-swapped with the load powered if maintenance is required
* 1+1 configuration: two SU40K models connected in parallel provide fail-safe redundancy or increased capacity
* High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology produce low input Total Harmonic Distortion (THDi)
* Low THDi (less than 3%) saves installation costs by allowing 1:1 generator sizing
* Extremely efficient operation (up to 96%) saves money by lowering electricity consumption
* True on-line, double conversion UPS with IGBT technology provides pure sine wave AC output at all times
* Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
* Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
* 40,000VA/32,000W power capacity with 3-phase, hardwire 120/208VAC input/output connections
* Features a wide input voltage correction range: 94-150/163-260VAC
* Internal power and battery components are combined in a single small-footprint tower module. Typical half-load/full-load runtimes are 13 min./5.5 min. Battery runtime can be extended with optional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C) with matching battery cabinets, available separately from Tripp Lite. Additional battery cabinets for extended runtime solutions also available; contact Tripp Lite for more information
* Front panel combination LCD/LED display includes a real-time event log screen with up to 500 events listed
* Dynamic battery management screen optimizes battery function to lengthen service life and allow cold restart of the UPS
* Built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server
* Accessory slot accepts an optional internal SNMP card (Model: SNMPWEBCARD) for remote shutdowns, reboots and more
* Emergency Power Off button turns UPS output OFF and disables Bypass output
* Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities
* 1-year limited repair warranty
* Start-up service program is recommended to enhance the reliability of the installation

Applications

* Ideal for protecting critical 120/208V equipment in computing, networking, telecommunications, manufacturing and healthcare environments.

Package Includes

* SU40K UPS System
* PowerAlert Software and cabling
* Parallel cable (for 1+1 operation)
* Instruction manual and startup checklist
* Warranty information