Toshiba HCV-5HAL Vacuum Contactor
Toshiba Updated: 2007-07-18400 Amp 2300-7200 Volts (Medium Voltage) The HCV-5HA, the first vacuum contactor produced in Houston, Texas, was also the first Toshiba vacuum contactor to incorporate an electronic drive unit to power the operating coils. This solid state design eliminated the economizing resistors and improved the reliability of the coil circuit. The contactor is available in either electrically maintained or latched type version. The compact size and high performance, as well as being available in a drawout design, has helped many OEMs and end-users replace old air-break contactors and breakers.
CONTACTOR MODEL HCV-5HA HCV-5HAL* CV-10HA CV-10HB HCV-6KAU HCV-6KALU*
Rated Voltage 2400/4200/6900V(7.2kV max) 12/15kV 12kV**** 2400/4200/6900V(7.2kV max)
Rated Operational Current 400A 320A 720A
Rated Thermal Current - 450A -
Interrupting Current 7000A (4.5kA @7.2kV) 5kA/4kA 5000A 7200A
Rated Short-time Withstand Cur. - 5000A - 1 sec -
Rated Peak Withstand Current - 12500A -
Short-circuit Making/Breaking Current - 5kA/4kA 5kA -
0-3min.-CO-3min.-CO
Class E1 MVA 25/50 (36/60) 120 30/60/85
Class E2 MVA 200/400/570 1200MVA 200/400/600
Short Time Current 2400A -30s 1920A - 30s 4320A - 30s
4000A -12s 8000A - 1s (4800A - 1s) 10800A - 1s
6300A - 2s -
Overcurrent Strength (Peak Value) 85kA (PEAK) See Coordination Below 85kA (PEAK)
Coordination w/Current-Limiting Fuses - Short-circuit Current 40kA
Cut-off Current 50kA Peak -
Switching Frequency 1200/Hr 300/Hr 300/Hr 120/Hr 600/Hr 300/Hr
Mechanical Life*** 2.5M 250k 250k 1M 200k
Electrical Life*** 250k 250k 100k 200k
Impulse Withstand 60kV 75kV 60kV
Dielectric Strength 22kV-1 Minute 28kV-1 Min (42kV)** 22kV-1 Minute
ClosingTime 80 ms or Less 130 - 140 ms or Less 80-100 ms
Opening Time 25 ms or Less 30 - 40 ms or Less 40-55 ms
Arcing Time 10 ms or Less 10 ms or Less 10 ms or Less
Pick-Up Voltage 85% (Hot) - 70 % (Cold) AC or DC
Drop-Out Voltage 50%(Hot) - 40% (Cold) AC or DC
Tripping Voltage 60% or less of Coil Rating DC (cold)
Control Voltage Standard 120Vac 50/60 Hz 100-240Vac/100-250Vdc l 115-240Vac/125-250Vdc
Optional 240Vac/125Vdc/250Vdc - -
Control Circuit Burden Closing 670VA (AC) - 700W(DC) 1150VA(AC)/1200W(DC) 840VA 875W
Holding 85VA(AC) - 85W (DC) 80VA (AC)/90W(DC) 48VA -
Tripping* 4.8A (DC)Max 4.0A (DC) Max - 4.8A Max
Auxiliary Contact Ratings Arrangement 3NO-3NC 2NO-3NC 4NO-2NC 2NO-1NC 3NO-3NC 2NO-2NC
Current 10A (A600)
Voltage 600V Max - 48V Min
AC 720VA (P.F. 0.35)
DC 60W (L/R 150 ms)
Application Conditions Altitude w/o Derate Lower than 6600ft (2000m) Lower than 3300ft
(1000m)
Ambient -5 to + 40°C
Relative Humidity 45 to 85%
Vibration 20 Hz - 1 G
Shock 30 G
Weight - lbs. (kg) 43 (19.5) 44 (20) 88 (40) 91 (41) 60 (27) 62 (28)
HCV-5HA Instruction Manual
Low & Medium Voltage Vacuum Contactors Brochure
HCV-5HA(L) Outline Drawing
Related Manuals
Toshiba VHA Series Vacuum Circuit Breaker
Toshiba HCV-6KALU Vacuum Contactor
Toshiba VJB Series Vacuum Circuit Breaker
Toshiba HCV-1JBU/1KAU Vacuum Contactor
Toshiba VK/HVK Series Vacuum Circuit Breaker
Toshiba CV-10 Vacuum Contactor
Toshiba Model RC820 Solid State Motor Protection Relay
Toshiba VZ Series Vacuum Circuit Breaker
Toshiba Model RC803 Overcurrent/Undercurrent Electronic Relay
Toshiba HV6 Series Vacuum Circuit Breaker
Toshiba Model RTM20 RTD Monitor
Toshiba Model S2E21 Protection Relay Multifunction Motor Electronic Relay