Toshiba Eagle0800U/Eagle0404U/Eagle0201U I/O Converter

Toshiba Updated: 2007-07-18
Toshiba Eagle0800U/Eagle0404U/Eagle0201U I/O Converter

The Eagle I/O is universal serial analog I/O. For the analog inputs, the Eagle I/O performs the A to D (analog to digital) conversion and loads a digital value directly into a T1 register. For analog outputs, the Eagle I/O reads a digital value out of a T1 register and performs a D to A (digital to analog conversion). Analog signal types and PLC registers are defined using simple setup software.

Key Features

Eagle I/O Specifications
Communication Ports:  PLC  Connects to T1 Programming Port
IBM Connects to Computer for Setup - Connects to OIS for PLC Access
Temperature:  Operating: 0?to 50?C Storage: -25?to 80?C
Humidity:  10% to 90% Non condensing
Immunity to ESD:  Level 3 per IEC 61000-4-2
Immunity to Transients:  Level 3 per IEC 61000-4-4
Radiated Susceptibility:  Level 3 per IEC 61000-4-3
Emissions:  EN55011 CISPR A
Certifications:  CE, CSA
Isolation:  Analog isolated from Digital, no isolation between channels.
Size  Eagle 0800 & 0404 155mm x 102mm x 48mm
Eagle 0201 94mm x 42mm x 47 mm
Mounting:  DIN rail or through hole
Weight  Eagle 0800 & 0404: 0.5 kg
Eagle 020:1 02 kg
Analog Inputs
Part Number:  See Order Numbers Below
I/O Registers Assigned:  None (Uses Data Registers, 1 Register per Channel Designated by Sfwr)
Input Range: Thermocouple Resolution  J, K, R, S, T, E, N, & B . 0-100 mV, Cold Junction Compensation Error 1? maximum, 0.5?C typical.
Input Range: RTD Resolution  PT100 (0.00395 and 0.00385), 0.5ma. Range: -200?to 800? C 3 Wire Compensation, Current Sense
Input Range:  Voltage 0-100 mV, 0-10 V (via PLC scaling/external shunt resistor)
Current  0-20 mA
Resolution  12 bit
Analog Outputs
Part Number:  See Order Numbers Below
I/O Registers Assigned:  None (Uses Data Registers, 1 Register per Channel Designated by Sfwr)
Output Range:  Voltage  0-10 V, Minimum Load = 400 ohm
Current  4-20 mA Maximum Load = 500 ohm